Enhanced Redundancy System Checklists

Chassis Configuration Checklist

Topic

Page

Chassis Configuration Checklist

277

Remote I/O Checklist

278

Redundancy Module Checklist

278

ControlLogix Controller Checklist

279

ControlNet Checklist

279

EtherNet/IP Module Checklist

280

Project and Programming Checklist

281

Requirement
Chassis used for the redundant pair are the same size, for example, both are 1756-A7, 7-slot chassis.

Only these modules are used in the redundant chassis:
ControlLogix controllers, catalog numbers 1756-L61, 1756-L62, 1756-L63, 1756-L63XT,1756-L64, 1756-L65, 1756-L71, 1756-L72, 1756-L73, 1756-L73XT, 1756-L74,

1756-L75

ControlNet communication modules, catalog numbers 1756-CN2/B, 1756-CN2R/B, 1756-CN2RXT
EtherNet/IP communication modules, catalog numbers 1756-EN2T,1756-EN2TXT, 1756-EN2TR, 1756-EN2F
Redundancy modules, catalog numbers 1756-RM, 1756-RMXT, 1756-RM2/A, 1756-RM2XT
Each chassis of the pair is comprised of identical modules that are of identical redundancy firmware revisions, series, and memory sizes.

(1)

Partner modules are placed in same slots of both chassis of the redundant pair (for example, the 1756-L63 is placed in slot 0 of both chassis).

I/O modules are not placed in the redundant chassis.

Seven or fewer communication modules of any type or combination are used in each redundant chassis.

(1) There are some exceptions to this requirement. For more information, see

Redundant Chassis on page 28

.