Upgrade from a Standard Redundancy System or to Another Enhanced Redundancy System

Appendix C

Step 1: Before You Begin

Consider these points before you begin upgrading your enhanced redundancy

system to a new revision.

During the upgrade procedures, you cannot use RSLogix 5000 software to

change the mode of the controller. Instead, use the mode switch on the

front of the controller.

Leave RSNetWorx™ for ControlNet software closed or offline throughout

this procedure. If the software is open or online, you see errors in the

RSNetWorx for ControlNet software during the upgrade process.

Remember the following when completing the tasks described in the rest

of this section:

Do not make any changes to the RSLogix 5000 project other than

those identified in these tasks.

Verify that no one will be or is making changes to the project.
Do not use a FactoryTalk Batch Server to change equipment phase-

states when upgrading your enhanced redundancy system.

Step 2: Upgrade the Workstation Software

Before you download and upgrade software for your redundant system, use one

of these methods to fully shut down RSLinx Classic software.

Right-click the RSLinx Classic icon in the notification area of the screen

and choose Shutdown RSLinx Classic.

With RSLinx Classic software open, from the File menu, choose Exit and

Shutdown.

Install the software required for your redundant system configuration. See

Software Requirements

on

page 49

for software versions required for use with

this enhanced redundancy system revision.

Use the installation instructions or release notes provided with each software

version for installation procedures and requirements.