Program the Redundant Controller

For example, if your application uses DINTs that you use only as constants to

initialize your logic, BOOLs that you update every scan, and REALs that you

update every second, you can create a separate User-Defined Data Type for each

type of tag that is used at different points in the application. Using separate User-

Defined Data Types for each group, rather than grouping all of the tags together

in one User-Defined Data Type, helps to minimize the amount of data

transferred during the crossload.

Use DINT Tags Instead of SINT or INT Tags when Possible

We recommend that you use the DINT data type instead of the SINT or INT

data types because the controller usually works with 32-bit values (DINTs or

REALs). When processing, the controller converts SINT or INT tag values to

DINT or REAL values. When processing is complete, the controller converts the

value back to a SINT or INT value.

The controller automatically converts these data types while executing and

processing a program. No additional programming is required. However, while

this conversion process is transparent to you, it does require additional processing

time that impacts your program scan time and your switchover time.

Figure 43 - Tags Grouped into User-Defined Data Types by

Frequency of Use

Figure 43 - Tags in One User-Defined Data Type