Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

Chapter 9

Troubleshoot a Redundant System

7. After you have located an event entry related to the anomaly you are

troubleshooting, double-click the event to view Extended Event

Information.

8. View the Description and Extended Data Definitions.

The Description and Extended Data Definitions can be used to obtain

further event information and may indicate a recovery method.

TIP

You can also use the Log Time column to identify a significant event. Scan
within a time range that corresponds to the time an event was reported or

annunciated.
In addition, you can also attempt to identify events by finding differences
between times logged. Such gaps in time often identify events that require

troubleshooting. When troubleshooting by identifying gaps in the time
entries, remember that gaps in months, days, or minutes may indicate a
significant change to the system.
Not all events logged are indicative of an anomaly that needs to be
corrected. For example, events classified as Minor Faults do not warrant
corrective behavior unless they occur just before a switchover, major fault,

or state change and can be identified as contributing to successive events.

Double-click to view more information.

The Description provides more

information about the state change that

occurred.

No recovery method is described. This

indicates that action is not required in

response to this event.

2

2

2

2

2

2

2

2