Chapter 6

Configure the Redundancy Modules

The chassis platform configuration identifies the common operating platform of

the modules in the redundant chassis and applies to all redundancy modules. It

may be one of the following values depending on the redundancy release installed

in the system and the type of communication modules running in the redundant

chassis.

Determine if Further

Configuration is Required

The default configuration of the redundancy modules lets you synchronize your

redundant chassis without additional configuration if you are using a basic

redundant chassis pair.

However, some applications and uses of the redundancy system can require

additional configuration. For example, you must use the RMCT for additional

configuration if you need to complete any of these tasks:

Set the redundancy modules to a different time or date (recommended).
Program your controller to control the redundant system.
Change the redundancy synchronization options of the redundant system.
Change the synchronization states of your redundant chassis.
Conduct a test switchover.
Complete a firmware update of a module in the redundant chassis while

the system is online.

If you need to complete any of these tasks, reference the sections that follow.

Table 16 - Chassis Platform Configuration

Type

Description

Standard

The redundant chassis is operating on a Standard

platform. Modules supported in redundancy release

revisions 16.057, 16.056, 16.053, and 16.050 and releases

earlier than revision 16 comprise the standard platform.

Enhanced

The redundant chassis is operating on an Enhanced

platform. Modules supported in redundancy release

revision 16.054 and all releases of revision 16.080 and

later comprise the enhanced platform.

Hybrid

The redundant chassis contains a mix of modules

belonging to standard and enhanced platforms. All Hybrid

platforms are an unsupported redundant system

configuration.