Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

255

Upgrade from a Standard Redundancy System or to Another Enhanced Redundancy System

Appendix C

7. Click the Synchronization tab

.

8. Click Disqualify Secondary, then click Yes.

The secondary chassis is disqualified as indicated by the RMCT at the

bottom-left of the RMCT and on the redundancy module’s status display.

9. Click OK and close the RMCT.

Closing the RMCT helps prevent a timeout from occurring when the

redundancy module’s firmware is upgraded.

Step 7: Upgrade the Primary Chassis Redundancy Module Firmware

Wait 45 seconds before you begin updating the 1756-RM firmware. During this

time, the redundancy module conducts internal operations to prepare for an

upgrade.

1. Launch ControlFLASH software and click Next.
2. Select the redundancy module catalog number and click Next.

Status in RMCT

1756-RM2/A

1756-RM/B