Chapter 5

Configure the ControlNet Network

Keep these points in mind when you use produced and consumed connections

over a ControlNet network in an enhanced redundancy system:

During a switchover, the connection for tags that are consumed from a

redundant controller can drop briefly.

The data does not update.
The logic acts on the last data that it received.

After the switchover, the connection is reestablished and the data begins to

update again.

You cannot bridge produced and consumed tags over two networks. For

two controllers to share produced or consumed tags, both must be

attached to the same network.

Produced and consumed tags use connections in both the controllers and

the communication modules being used.

Because the use of produced and consumed tags uses connections, the

number of connections available for other tasks, such as the exchange of

I/O data, is reduced.

The number of connections available in a system depends on controller

type and network communication modules used. Closely track the

number of produced and consumed connections to leave as many as

necessary for other system tasks.