Chapter 6

Configure the Redundancy Modules

Event Log Tab

The Event Log tab provides a history of events that have occurred on the

redundant chassis.

These system events are indicated in the event logs:

Qualification stages entered and completed

Module insertion/removal

Firmware errors

Communication events and errors

Configuration changes

Other system events that affect qualification and synchronization

The Event Log tab can be customized to view the log specific to only one chassis

or the event logs of both redundant chassis. You can alter your view of the event

logs by changing the Auto-Update and Partner Log parameters.

Figure 29 - Settings for Event Log Views

IMPORTANT

The events logged in this tab are not always indicative of an error. Many of

the events logged are informational only.
To determine if additional action or troubleshooting is required in response
to an event, see the

Event Classifications

table on

page 121

.

Table 20 - Settings for Event Log Views

Use this setting

To

Auto-Update

Keep the log from updating while you’re viewing it.

Partner Log

View only the event log for the module you are accessing.

Check On to keep the log updating automatically.

Check Close to view only the log of one redundancy module.