Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

47

Design an Enhanced Redundancy System

Chapter 2

HMI Connected via a ControlNet Network

This table describes redundant system considerations specific to the HMI being

used on the ControlNet network.

HMI connected to a primary chassis exclusively over a ControlNet network or

bridge from an EtherNet/IP network to a ControlNet network maintains its

connections during a switchover.

Type of HMI Used

Considerations

PanelView Standard terminal
PanelView 1000e or PanelView 1400e

terminal

If your HMI communicates via unscheduled communication, use

four terminals per controller.

If your HMI does not communicate via unscheduled

communication, use the number of terminals required for your

application.

PanelView Plus terminal
VersaView industrial computer running a

Windows CE operating system

Set aside connections for each PanelView Plus or VersaView CE

terminal.

FactoryTalk View Supervisory Edition

software with RSLinx Classic software,

version 2.52 or later

RSView32 software
Any other HMI client software that uses

RSLinx Classic software, version 2.52 or

later

Limit the number of RSLinx servers that a controller uses to 1 (ideal) to

3 (maximum).

In this module

Reserve

Controller

5 connections

1756-CN2/B,

1756-CN2R/B

5 connections