About Enhanced Redundancy Systems
I/O Modules in Enhanced Redundancy Systems
In an enhanced redundancy system, you can use only I/O modules in a
remote chassis. You cannot use I/O modules in the redundant chassis pair.
This table describes differences in network use for I/O in enhanced redundancy
systems.
For more information on using remote and 1715 redundant I/O over an
EtherNet network, see
System User Manual, publication
.
Remote I/O Module Placement
Available with Enhanced System, Revision 19.052, 19.053,
or 20.054
Available with Enhanced System, Revision 16.081 or
Earlier
EtherNet/IP I/O network
1715 Redundant I/O System
ControlNet network
DeviceNet network
(1)
Data Highway Plus
(1)
Universal Remote I/O
(1)
(1) In an enhanced redundancy system, you can access remote I/O modules on this network only via a ControlNet or EtherNet/IP network bridge.