Upgrade from a Standard Redundancy System or to Another Enhanced Redundancy System

Appendix C

Step 12: Synchronize the Redundant Chassis

Complete these steps to synchronize the redundant chassis after firmware in both

chassis have been upgraded to the same revision.

1. Launch the RMCT for the redundancy module in the primary chassis by

right-clicking on the module in RSLinx Classic software and selecting

Module Configuration.

2. From the Auto-Synchronization pull-down menu, choose the frequency

that suits your application.

3. Click Apply, then click Yes.
4. Synchronize the chassis.

5. Set the redundancy module date and time according to your preference.
6. Click OK.
7. Close the RMCT.

Your redundant system firmware upgrade is now complete.