Set the node address switches to 00, Insert the module into the chassis – Rockwell Automation 1756-RMxx ControlLogix Enhanced Redundancy System User Manual User Manual

Page 103

Advertising
background image

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

103

Configure the ControlNet Network

Chapter 5

To replace a ControlNet module that has been configured and scheduled on the

ControlNet network, remove the existing module and insert a 1756-CN2/B,

1756-CN2R/B, or 1756-CN2RXT module. The module you are inserting must

be unconfigured or have a keeper signature of all zeros.

After being inserted and connected to the ControlNet network, the

unconfigured 1756-CN2, 1756-CN2R, and 1756-CN2RXT modules crossload

the appropriate configuration from the active keeper on the ControlNet network

and become configured with the appropriate keeper signature.

TIP

To clear the keeper signature of a 1756-CN2, 1756-CN2R, or 1756-CN2RXT
module, complete these steps.

1.Disconnect the module from the ControlNet network and remove it from the

chassis.

2.Set the node address switches to 00.

3.Insert the module back into the chassis and wait for the status display to indicate

Reset Complete.

4.Remove the module and set the node address switches to the intended node

address.

5.Insert the module into the chassis.