Change the system overhead time slice – Rockwell Automation 1756-RMxx ControlLogix Enhanced Redundancy System User Manual User Manual

Page 166

Advertising
background image

166

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

Chapter 7

Program the Redundant Controller

Change the System Overhead Time Slice

To change the System Overhead Time Slice, access the Controller Properties

dialog box and click the Advanced tab. You can enter your System Overhead

Time Slice value.

Options for During the Unused System Overhead Time Slice

Enable the Run Continuous Task option (default setting) if you want the

controller to revert to running the continuous task as soon as the communication

servicing task has no pending activity. This has the effect of only using the

allocated communication servicing time if there is a need for it.

When the Run Continuous Task option enabled, the controller immediately

returns to the continuous task.

Use the Reserve for System Task option to allocate the entire 1 ms of the System

Overhead Time Slice for service communication - even if no service

communication or background tasks need to be executed. You might choose to

use this option without service communication or background tasks to simulate a

communication load on the controller during design and programming. Use this

setting for testing purposes only.