Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

175

Program the Redundant Controller

Chapter 7

Set the Redundancy Module Date and Time

To set the wallclock time of the 1756-RM module, use the MSG instruction

parameters listed in this table.

Set the Task Watchdog

Watchdog times set for tasks in redundancy applications must be larger than

watchdog times set for tasks in nonredundancy applications because more time is

required to conduct crossloads and synchronization.

An increase in the required watchdog time is also a result of the way programs are

executed in the event of a switchover. A program or programs may be executed a

second time after switchover, depending on when in the task or program the

switchover occurs and where in the task crossload and synchronization occurs.

If a program is executed a second time, the length of time required for the

program scan is increased. However, the watchdog timer is not reset and

continues to countdown from the beginning of the task that was started by the

old primary controller. Therefore, the watchdog timer must be configured to

account for the potential of additional program scans.

Table 33 - Set Wallclock Time

In this tab

Edit this element

To use this value

Configuration

Message Type

CIP Generic

Service Type

Custom

Service Code

10

Class

8b

Instance

1

Attribute

b

Source Element

WallClockTime[0]
WallClockTime
is a DINT[2] array that stores the

CurrentValue of the WALLCLOCKTIME object

Source Length

8

Destination Element

None - no value needed.

Communication

Path

Browse for the path to the 1756-RM or

1756-RMXT redundancy module.

Connected box

Leave the Connected checkbox unchecked.