Default crossload and synchronization settings, Recommended task types, Continuous task after switchover – Rockwell Automation 1756-RMxx ControlLogix Enhanced Redundancy System User Manual User Manual

Page 145

Advertising
background image

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

145

Program the Redundant Controller

Chapter 7

Default Crossload and Synchronization Settings

The default setting for a program in a redundant project is for a crossload to

occur at the end of each program execution. However, for an equipment phase,

the default is that the crossload not execute at the end of the phase.

Before you change the default crossload and synchronization settings, read the

sections that follow so you have a complete understanding of the implications.

For information about how to change the point in a task where a crossload

occurs, see

Changing Crossload and Synchronization Settings on page 144

.

Recommended Task Types

To avoid anomalies after a switchover occurs, we recommend that you use only

one of these task configurations when programming your redundant controllers.

Use either of the following:

One continuous task
Multiple periodic tasks with one task at the highest priority

The sections that follow explain the impact of crossloads and synchronization

after a switchover based on the task structure you use.

Continuous Task After Switchover

After a switchover occurs within a controller project that contains only a

continuous task, the new primary begins executing at the last crossload and

synchronization point. Depending on your crossload and synchronization

setting, the program that the new primary controller begins with may be

the following:

The program that was interrupted by the switchover
The program that immediately follows the last crossload and

synchronization point

Advertising