8–6

Creating Push Buttons

Publication 2711-6.0

Write Tag

Specifies the name of the tag address to write the single bit or value.
Edit the tag definition using the Edit Tag button or the Tag Editor.

Indicator Tag

Specifies the name of a tag address that controls when the push
button changes appearance with each state. Each state can have
unique visual characteristics (inner text, inner graphic, fill). Edit the
tag definition using the Edit Tag button or the Tag Editor.

This Option

Means

No Indicator Tag (default)

Push button changes to next state when pressed.

Indicator Tag
same as Write Tag

Push button changes state after bit or value is written
to the Write Tag address.

Indicator Tag
different from Write Tag

Push button changes state after:

bit or value is written to the Write Tag address and

state value is read from Indicator Tag address.

Same Write Tag
& Indicator Tag

No Indicator Tag

Different Write Tag
& Indicator Tag

➁➂

Step

Description

Button pressed

Step

Description


Bit or value written

Button pressed

Button changes to

Step

Description

Bit or value written
to Indicator Tag address

Button pressed
Bit or value written

Button changes to

to Write Tag address

next state based on value

to Write Tag address

next state based on value

Button changes to
next state

INITIAL
STATE

ООО

ООО

ООО

NEXT

STATE

INITIAL
STATE

ОООО

ОООО

ОООО

NEXT

STATE

INITIAL
STATE

ООО

ООО

ООО

NEXT

STATE

read from Write Tag address

read from Indicator Tag
address

Important:

If the indicator tag and write tag are different, the
indicator state is controlled by the controller program
regardless of the push button state. For example, the
indicator tag address may specify that push button state
1 is displayed while the write tag address is at state 0.