Rockwell Automation 2711-ND3 PanelBuilder v2.60 Software User Manual User Manual

Page 461

Advertising
background image

Validation Messages

E–7

Publication 2711-6.0

Validation Message

What to do

Meaning

Terminal (name) is not configured in Terminal
Setup – Comms. Setup – Runtime Comm.
Port is wrong type.

The terminal is not configured properly.

Open the Project Management dialog and
delete the terminal device from the project.
Then open the Terminal Setup dialog and
reconfigure the terminal.

Terminal (name) max node number (value)
not valid

The maximum node number is invalid. The
maximum node number must be in the range
of the terminal node number to 31.

From the Setup tab in the Terminal Setup
dialog, press the Comms. Setup button to
change the maximum node number.

Terminal name not assigned

The terminal isn’t assigned a terminal name.

From the Setup tab in the Terminal Setup
dialog, enter a name for the terminal.

Terminal (name) node number is not valid

The node number of the terminal must be in
the range of 1 to 31.

From the Setup tab in the Terminal Setup
dialog, press Comms. Setup button to change
the node number of the terminal.

Terminal selected in Terminal Setup does not
match Application type.

The wrong catalog number was selected for
the terminal name in Terminal Setup.

From the Terminal Setup dialog, select the
correct terminal type to match the application
(DH-485 or Remote I/O).

Terminal Status and Control cannot use the
same tag for the same purpose.

The same tag is being used for a control tag
and a status tag in the Terminal Setup dialog.
Control and status tags must be different.

From the Control or Status tab in Terminal
Setup correct the tag duplication.

Text foreground color is the same as its
background color.

Text foreground and background colors are
the same making the text invisible.

Change foreground and background colors so
they are not identical.

Text string contains character(s) from external
font file, selected font size is invalid.

Double byte external font is in use and text
contains double byte characters while an
internal font size is selected.

Specify an external font size.

The address string data type does not match
the tag data type

The tag address doesn’t match the data type
of the tag. For example, the tag address is
B3:0/2 but the tag data type is signed integer.

From the tag editor, correct the mismatch
between the tag address and the data type of
the tag.

The initial state in this device refuses operator
entry.

The initial (power-up) state for the piloted
control list does not allow operator access.

Open the object’s dialog and set the initial
state Access to “User and LC” or “User Only”.

The remote tags must be different from each
other.

Each remote tag must be unique for an alarm
setup.

Make the remote tags unique within the
application.

Time Format does not support double-byte
characters.

Double-byte font selected for Time Format.

Select a single byte size font.

Trigger and Remote Ack Tag have different
tag types.

The data type for these tags are not identical.

Change the tag data types so they are the
same.

Trigger cannot be same as the acknowledge
or handshake tags.

The trigger tag is the same as the
acknowledge or handshake tag for this
trigger.

Specify a unique tag for trigger, acknowledge
and handshake tags.

Trigger Name not Unique

Two triggers are using the same trigger tag
name.

Change trigger tag names so they are not the
same.

Trigger Tag duplication

Two triggers are using the same trigger tag
name.

Change trigger tag names so they are not the
same.

Trigger Tag same as LC Clear All Tag.

The Trigger Tag is the same as the Clear All
tag specified on the Alarm Setup screen.

Change tags so they are not identical.

Trigger’s Ack Tag same as LC Ack All Tag

The Trigger Alarm Ack Tag is the same as the
Ack All tag specified on the Alarm Setup
screen.

Change tags so they are not identical.

Trigger’s Remote Ack Tag same as LC Ack All
Tag.

The alarm trigger’s remote acknowledgment
tag is the same as the controller Ack All tag.

Change tags so they are not identical.

Unable to initialize Protocol Translation
Server. Invalid address for Block Transfer
Channel Num (number)

The address of the block transfer is invalid.
You may have entered a PLC address where
an SLC address was expected or an SLC
address where a PLC address was expected.

In the Block Transfer dialog, enter the correct
address for the specified block transfer
number.

Advertising