Alarm examples, Operator acknowledges alarm – Rockwell Automation 2711-ND3 PanelBuilder v2.60 Software User Manual User Manual
Page 250

15–28
Creating Alarms
Publication 2711-6.0
This section provides examples of different alarm configurations
ranging from simple to more complex.
Operator Acknowledges Alarm
In the example below, the operator presses the Ack button to
acknowledge an alarm. Because the Acknowledge tag is not defined
for the trigger, the controller is not notified. Optional Fields are not
enabled for the alarm triggers.
Msg B
Ack
➀
The PanelView reads the value 15 from the Trigger
(Pump) address in the controller. This value trig-
gers alarm Msg B.
Alarm Configuration
– Four alarms are assigned to the Pump trigger tag, each with a different trigger value
– All alarm messages are configured to display in the Alarm Banner and must be acknowledged
➂ Alarm Banner displays alarm text.
➁ Alarm Msg B is placed in the List
➃ Operator presses Ack button
–Alarm Msg B is flagged acknowledged in the Alarm List
–Alarm Banner is cleared from display
Msg B
Ack
Alarm List
Pump
Msg B
Alarm Examples