4–7

Communications Overview

Publication 2711-6.0

Remote I/O Scan Group

A Remote I/O scan groups consists of words or address contained
within a discrete I/O rack or within a block transfer. For example, an
application with a full rack, block transfer read N7:0, length 64 and a
block transfer write N7:128, length 62 has these scan groups:

O:010 – O:017

I:010 – I:017

N7:0 – N7:63

N7:64 – N7:127

N7:128 – N7:190

Controller Types

The PanelView Remote I/O terminals communicate with the
controllers below. For each controller, the table lists supported rack
numbers and support for Pass-Through and block transfers.

Controller/Scanner

Lowest

Rack #

Highest

Rack #

Pass-Through Support

Block Transfer Support

IBM PC 6008-SI

IBM PC 6008-SI
VME 6008-SV

EC

S 6008-S

0

7

No

Yes

V E 6008-SV
DEC QBUS 6008-SQ

0

7

No

Yes

PLC 5/11

3

3

All Series, All Revisions

Yes

PLC 5/15

1

3

Series B, Revision N or later

Yes

PLC 5/20

1

3

All Series, All Revisions

Yes

PLC 5/25

1

7

Series A, Revision J or later

Yes

PLC 5/30

1

7

Series A, Revision B or later

Yes

PLC 5/40

1

17

octal

Series A, Revision E or later
Series B, Revision B or later

Yes

PLC 5/60
PLC 5/80

1

27

octal

Series A, Revision E or later
Series B, Revision B or later

Yes

SLC 1747-SN Series A

0

3

No

No

SLC 1747-SN Series B

0

3

Yes

Yes

Other 1771-SN Subsystem

1

7

No

No