Chapter

12

Publication 2711-6.0

Creating Bar Graphs, Indicators,
Numeric Displays

Bar graphs, indicators and numeric data displays show a numeric
value or a graphic representation of data stored at a controller tag
address. This chapter contains the following sections:

Section

Page

Helpful Hints

12–1

Scaling Data

12–2

Error States

12–3

Bar Graphs

12–4

Numeric Data Displays

12–9

Multistate Indicators

12–12

List Indicators

12–18

When creating bar graphs, indicators and displays, consider:

Indicators reading a value do not have a “dead band” in which a
range of values are interpreted as a single state. For most
applications, the controller ladder logic should allow a range of
values above and/or below the specified value for each state to be
interpreted as the same state.

Multistate indicators support up to 2,000 states or entries
(numbered 0-1,999).

List indicators support up to 255 states or entries (numbered
0-254).

For multistate or list indicators, use only the number of states or
entries required by the application.

Multistate indicators include an error state (State E). The error
state notifies an operator that the data read isn’t within the
expected ranges.

Chapter Objectives

Helpful Hints