Rockwell Automation 2711-ND3 PanelBuilder v2.60 Software User Manual User Manual

Page 477

Advertising
background image

Internal Read Only Tags

G–3

Publication 2711-6.0

DH-485 Tags

Tag Name

Data Type

Value Range

Description

@Read_BaudRate

Unsigned Integer

1 to 4

1 = 1200, 2 = 2400, 3 = 9600, 4 = 19200

@Read_MaxNodeAddress

Unsigned Integer

1 to 31

@Read_MemCardStatus

Unsigned Integer

0 to 3

0 = Valid memory card format
1 = Incorrect memory card format
2 = No memory card installed
3 = No applications on memory card

@Read_NodeAddress

Unsigned Integer

0 to 31

@Read_SerCommStatus

Unsigned Integer

0 to 5

0 = Communication link is ok
1 = PanelView terminal is off the link
2 = Scanned node not found
4 = I/O error (Invalid I/O form controller)
5 = Duplicate node address

Remote I/O Tags

Remote I/O Tag Name

Data Type

Value Range

Description

@SRIO_RackNumber

Unsigned Integer

0 to 62

@SRIO_RackSize

Unsigned Integer

0 to 3

0 = 1/4
1 = 1/2
2 = 3/4
3 = Full

@SRIO_DataRate

Unsigned Integer

0 to 2

0 = 57.6K
1 = 115.2K
2 = 230.4K

@SRIO_Module

Unsigned Integer

0 to 3

0 = Module Group 0,1
1 = Module Group 2,3
2 = Module Group 4,5
3 = Module Group 6,7

@SRIO_LastRack

Unsigned Integer

0 or 1

0 = False
1 = True

@SRIO_BlockTransferReadEnable

Unsigned Integer

0 or 1

0 = Disable
1 = Enable

@SRIO_BlockTransferWriteEnable

Unsigned Integer

0 or 1

0 = Disable
1 = Enable

@SRIO_BlockTransferTimeout

Unsigned Integer

0 to 65535

0 = No Timeout
1 to 65535 (in milliseconds)

@SRIO_PassThruEnabled

Unsigned Integer

0 or 1

0 = Disable
1 = Enable

@Read_SerCommStatus

Unsigned Integer

1 to 128

1 =Communications active
2 =Timeout in block transfer write from PLC
4 =Timeout in block transfer read
8 =Timeout in both block transfer write and block transfer read
16 =PLC offline
17 =Pass-Through occurring
32 =Communication with PLC failed
64 =Bad rack setup
128= PanelView RIO hardware failed startup tests failed