Block Transfer Write Example

The following example illustrates a block transfer write. The
PanelView terminal is assigned to rack #3, starting module group 0.
One of the PanelView objects, a bar graph display addressed as N7:0,
reads a portion of the data block being transferred.

BTW

(EN)

BLOCK TRANSFER WRITE
Rack

03

Group

0

Module

0

Control Block

N16:1

Data File

N7:0

Length

10

Continuous

N

The PLC receives and stores data from an
input device, in this example a flow sensor.

The PLC ladder logic program initiates a
block transfer of a data block (10 words)
containing the screen display data.

Bar Graph Object with
Tag Name ’Flow Rate’ = Address N7:5

The PanelView terminal receives the data and
determines the starting address for the write
operation by matching the block size with the
address entered in the Block Transfer dialog.

The PanelView updates the bar graph display
using the data from the controller.

Flow Rate
Transducer

Data
From
PLC

N7:5

10 WORDS

N7:0
N7:1
N7:2
N7:3
N7:4
N7:5
N7:6
N7:7
N7:8
N7:9

Flow Rate Data

The PanelView now carries a copy of that
segment of the logic controllers data table.

Tag Name = Flow Rate