Rockwell Automation 2711-ND3 PanelBuilder v2.60 Software User Manual User Manual

Page 338

Advertising
background image

20–6

Terminal and Communication Setup

Publication 2711-6.0

4. Under Terminal, edit the following parameters.

Use:

To:

Node Address

Select the station number (0 to 77 octal) of the
PanelView terminal on the DH+ link.

Baud Rate

Select the baud rate of the DH+ link. The baud
rates and maximum cable lengths for each rate
are:
57.6K

3,048 m (10,000 ft)

115.2K

1,524 m (5,000 ft)

230.4K

762 m (2,500 ft)

5. Under Network Nodes, edit the node parameters of the controller.

To insert a network node, right–click in the Node Name field and
select Insert Node from the menu. Click in a field to edit it.

Use:

To:

Node Name

Enter a unique name for the logic controller that
will communicate with the PanelView terminal on
the DH+ link.

Node Address

Select the station number (0 to 77 octal) of the
logic controller on the DH+ link.

Node Type

Select the type of logic controller that will
communicate with the PanelView terminal.

To delete a node, right-click in a node field and select Delete
Node from the shortcut menu. From this menu, you can also sort
multiple nodes by name, address, type or only modified nodes.

To copy, rename or delete devices from a project, use the Project
Management command. See page 21–4

.

6. Click OK to exit and return to the Terminal Setup dialog.

"