4–3

Communications Overview

Publication 2711-6.0

The DH+ PanelView terminals communicate with a PLC or SLC
5/04 controller on the Allen-Bradley DH+ link.

Addressing for a DH+ application is similar to a DH-485 application
except the DH+ link supports 64 nodes (0 - 77 octal) and higher baud
rates. The DH-485 link supports 32 nodes.

The DH+ parameters for the terminal and controller are defined in
the Communication Setup dialog (accessed from Terminal Setup
dialog).

Terminal Name is stored in
Project with Catalog Number
information.

PanelView 900
DH+Terminal
with RS-232 Printer Port

Network Node
SLC 5/04

PLC-5/25

PLC-5/10

PLC-5/30

PLC-5/11

PLC-5/40

PLC-5/12

PLC-5/60

PLC-5/15

PLC-5/80

PLC-5/20

Must match Node
Name in Tag Editor.

The following table defines DH+ parameters and defaults for a
PanelView DH+ terminal and logic controller.

DH+ Device

DH+ Parameter

Options

Default

Pane V ew Term na

Node Address

0 – 77 octal

2

PanelView Terminal

Baud Rate

57.6K, 115.2K, 230.4K

57.6 K

Node Name

User supplied

None

Network Node

Node Address

0 – 77 octal

1

Network Node

Node Type

See above figure

None

DH+ Communications