4–3
Communications Overview
Publication 2711-6.0
The DH+ PanelView terminals communicate with a PLC or SLC
5/04 controller on the Allen-Bradley DH+ link.
Addressing for a DH+ application is similar to a DH-485 application
except the DH+ link supports 64 nodes (0 - 77 octal) and higher baud
rates. The DH-485 link supports 32 nodes.
The DH+ parameters for the terminal and controller are defined in
the Communication Setup dialog (accessed from Terminal Setup
dialog).
Terminal Name is stored in
Project with Catalog Number
information.
PanelView 900
DH+Terminal
with RS-232 Printer Port
Network Node
SLC 5/04
PLC-5/25
PLC-5/10
PLC-5/30
PLC-5/11
PLC-5/40
PLC-5/12
PLC-5/60
PLC-5/15
PLC-5/80
PLC-5/20
Must match Node
Name in Tag Editor.
The following table defines DH+ parameters and defaults for a
PanelView DH+ terminal and logic controller.
DH+ Device
DH+ Parameter
Options
Default
Pane V ew Term na
Node Address
0 – 77 octal
2
PanelView Terminal
Baud Rate
57.6K, 115.2K, 230.4K
57.6 K
Node Name
User supplied
None
Network Node
Node Address
0 – 77 octal
1
Network Node
Node Type
See above figure
None
DH+ Communications