G–4

Publication 2711-6.0

ControlNet Tags

You can display the Network Update Time (NUT), UMAX Node,
SMAX Node and other data on a screen by assigning one of the
following read only tags to a display objet. You must use an ASCII
display for tags with a string data type.

Tag Name

Data Type

Description

@Read_DCNUTime

Unsigned Integer

Network Update Time (NUT) in milliseconds.

@Read_DCUMAX

Unsigned Integer

Unscheduled Maximum (UMAX) node address

@Read_DCSMAX

Unsigned Integer

Scheduled Maximum (SMAX) node address

@Read_curDCAddress

Unsigned Integer

Current Node Address

@Read_DCASANumber

String

CIP/ASA serial number of the PanelView

@Read_DCCommStatus

Unsigned Integer

Communication status number

@Read_DCFirmwareRev

String

ControlNet firmware revision number

@Read_DCNewAddress

Unsigned Integer

Terminal address to use after a reset

@Read_DCProtocol

String

Firmware build date

@Read_DCRedundancy

Unsigned Integer

LED status number. Indicates status of A and B cables.

@Read_DCScanDelay

Unsigned Integer

Scan delay in milliseconds (time between reads)

DeviceNet Tags

Tag Name

Data Type

Value Range

Description

@Read_DCB01

Unsigned Integer

0 or 1

0 = Hold in Reset, 1 = Reset and Continue Comms.

@Read_DCCommStatus

Unsigned Integer

0 to 13

0 = No connection
1 = Connection timed out.
3 = Cannot obtain Explicit–Client tag
4 = Zero length I/O message received
5 = Message overrun
11 = No network power
12 = Dup MAC failure
13 = Bus–Off interrupt occurred

@Read_DCInputSize

Unsigned Integer

0 to 64

Number of words sent to scanner from PanelView with
each I/O scan.

@Read_DCOutputSize

Unsigned Integer

0 to 64

Number of words sent to PanelView from scanner with
each I/O scan.

@Read_DCScanDelay

Unsigned Integer

0 to 65535

Delay scan of the Explicit-Client tags

@Read_DCAddress

Unsigned Integer

0 to 63

Address of PanelView on DeviceNet link.

@Read_DCBaudRate

Unsigned Integer

0 to 2

0 =125 Kbps, 1 = 255 Kbps, 2 = 500 Kbps

DF1 Tags

Tag Name

Data Type

Value Range

Description

@Read_DFX_ErrorDetectOption

Unsigned Integer

0 or 1

0 = BCC, 1 = CRC

@Read_DFX_HandshakeOption

Unsigned Integer

0 or 1

0 = Off, 1 = On

@Read_DFX_Parity

Unsigned Integer

0 to 2

0 = None, 1 = Even, 2 = Odd

@Read_DFX_PortMode

Unsigned Integer

0 – 3

0 = N-8-1, 1 = E-8-1, 2 = O-8-1, 3 = N-8-2

@Read_DFX_StopBits

Unsigned Integer

0, 2

0 = 1 Stop Bit, 2 = 2 Stop Bits

@Read_BaudRate

Unsigned Integer

2 to 6

2 = 1200, 3 = 2400, 4 = 4800,
5 = 9600, 6 = 19200

@Read_SerCommStatus

Unsigned Integer

0 to 2

0 = Connected, 1 = Offline, 2 = Hardware Failure

@Read_DFX_NodeAddress

Unsigned Integer

0 to 253

0 to 253