Rockwell Automation 2711-ND3 PanelBuilder v2.60 Software User Manual User Manual

Page 460

Advertising
background image

Validation Messages

E–6

Publication 2711-6.0

Validation Message

What to do

Meaning

Tag does not have a valid address in the
terminals assigned Discrete Rack or Block
Transfers.

The tag address is not in the I/O rack or the
block transfer(s) configured for the terminal.

Enter the correct tag address in Tag Editor or
reconfigure parameters in the Terminal Setup
(Communication Setup) dialog.

Tag (name) Initial Value entry must be integer.

The initial value for the specified tag was
entered with a decimal point (1.5). The initial
value must be an integer.

Enter an integer for the initial value.

Tag (name) is not included in the Alarm
Trigger’s scan group.

Rem Ack tag or embedded tag in alarm
message is not in the alarm trigger’s scan
group.

Verify the alarm trigger has a lower address
than the remote tag or embedded tags.

Tag (name) must be of type Bit

A value type tag was selected where a bit tag
must be used.

Select an appropriate tag.

Tag (name) must be of type Value

A bit tag was selected where a value tag must
be used.

Select an appropriate tag.

Tag (name) – No Device in Project Database
to match Nodename (name)

The Project database does not have a device
matching the node name for the specified tag.

Use Communication Setup to add the device
with the specified node name to the project or
enter the correct node name for the tag in the
Tag Editor.

Tag not of type Value or Bit

An inappropriate tag was selected.

Select an appropriate tag.

Tag/Object data type mismatch.

Data type of an object entered in the tag
editor must be compatible with the data
format of the value entered in the object’s
dialog.

Correct the discrepancy by opening the
object’s dialog or accessing the object’s tag
information.

Tag references device (name). This is not the
Logic Controller selected in Terminal Setup –
Comms. Setup

The node name field in the Tag Editor
references a controller that is invalid or does
not match the controller name in Terminal
Setup (Communication Setup dialog).

Change the node name to match the
controller name in the Communication Setup
dialog or select the correct controller name in
the Communication Setup dialog.

Target terminal can only handle (number) list
devices on one screen.

Screen contains more list objects than the
terminal can handle.

Remove one or more of the list objects from
the screen.

Terminal (name) has no RIO Block Transfer
Channel Information in the Project Database

Block transfers have not been defined for the
Remote I/O terminal.

From the Setup tab in the Terminal Setup
dialog, press the Comms. Setup button. Then
press the Block Transfer button to define
block transfer assignments for the terminal.

Terminal (name) has no RIO Rack Module
Group Information in the Project Database.

The terminal is not assigned to a rack or
module groups in the rack.

From the Setup tab (Terminal Setup dialog),
press the Comms. Setup button to define the
rack and module group for the terminal.

Terminal (name) is not configured in Terminal
Setup – Comms. Setup

Communication parameters have not been
defined for the terminal name defined on the
Setup tab in the Terminal Setup dialog.

From the Setup tab (Terminal Setup dialog),
press the Comms. Setup button to define
communication parameters for the terminal.

Terminal (name) is not configured in Terminal
Setup – Comms. Setup – Type Unknown

The terminal is not configured properly.

Open the Project Management dialog and
delete the terminal device from the project.
Then open the Terminal Setup dialog and
reconfigure the terminal.

Terminal (name) is not configured in Terminal
Setup–Comms. Setup–No Runtime Comm.
Port

The terminal is not configured properly.

Open the Project Management dialog and
delete the terminal device from the project.
Then open the Terminal Setup dialog and
reconfigure the terminal.

Terminal (name) is not configured in Terminal
Setup – Comms. Setup – Runtime Comm.
Port Not in Project database.

The terminal is not configured properly.

Open the Project Management dialog and
delete the terminal device from the project.
Then open the Terminal Setup dialog and
reconfigure the terminal.

Advertising