Validating and Transferring Applications
Publication 2711-6.0
DH-485 Pass-Through Setup
When you click the Setup button from the Download (or Upload)
Application dialog and the terminal is defined as a DH-485 terminal
with an RS-232 port, this dialog opens.
Note: If more than one COM port is configured with a DH+ driver,
the dialog will display available Ports. Select the appropriate port.
To configure DH-485 Pass-Through parameters:
1. Define the Pass-Through parameters as defined below.
2. Click OK to return to the Application Download dialog.
Use:
To:
Local Network
Gateway Node Address
Link ID
Specify the node address (0 to 76) of the SLC 5/04
controller or DH+/DH485 Gateway to which your computer
is connected.
Specify the unique ID number (1 – 65534) that identifies
the computer to controller (or DH+/DH485) link on the
DH+ network.
Remote Network
Terminal Address
Link ID
Specify the node address (0 to 31) of the PanelView
terminal on the DH-485 network to which you are
downloading an application.
Specify the unique ID number (1 – 65534) that identifies
the link between the controller and PanelView terminal on
the DH-485 network.