20–11

Terminal and Communication Setup

Publication 2711-6.0

Use block transfers on a Remote I/O link to transfer:

data or

applications from a computer on the DH+ network to a terminal
on the Remote I/O network using Pass-Through

You can create up to 10 block transfer channels, numbered 1 – 10.
Each channel is associated with a block transfer read or write
instruction (BTR or BTW) in the controller ladder logic.

To define block transfers:

1. Click the Block Transfer button from the Communication Setup

dialog.

If the controller/scanner does not support block transfers, the
Block Transfer button is dimmed.

2. Enter the block transfer parameters starting with 1.

Use:

To:

Enabled

Enable or disable the block transfer. The default is disabled.

Address

Specify the starting address of the block transfer in a native
SLC or PLC (Remote I/O) link.

Mode

Specify Read or Write.

Length

Specify the number of words (1–64) required by a block
transfer. The default is 64. A length of 63 is reserved for
Pass-Through.
Each block transfer must use a different starting address, length
and read/write mode.

3. Repeat step 2 for each additional block transfer required.

4. If downloading applications from a computer on the DH+

network, you must select the Pass-Through check box.

Note: If Pass-Through is not supported by controller, the check
box is dimmed.

Defining Block Transfers