4–8

Communications Overview

Publication 2711-6.0

Remote I/O Communication Parameters

Remote I/O communication parameters are defined in the
Communication Setup dialog which is accessed from the Terminal
Setup dialog.

Terminal Name is stored in Project
with Catalog Number information.

PanelView 900
Remote I/O Terminal
with RS-232 Printer Port

Must match Node
Name in Tag Editor.

The table below defines Remote I/O communication parameters for
the PanelView terminal.

Remote I/O

Device

Remote I/O

Parameter

Description

Options

PLC/S anner

Type

Type of PLC controller/scanner that will
communicate with the PanelView
Remote I/O terminal.

See table on
page 4–7.

PLC/Scanner

Name

Unique name assigned to controller.
This name is also used in the Node
Name field in the Tag Editor.

User supplied

Rack Address

Unique address of PanelView terminal
on Remote I/O link.

0 – 27

octal

Pane V ew

Module Group

Module groups occupied by PanelView
terminal in the rack. The Module groups
must be contiguous.

0,1 2,3 4,5 6,7

PanelView

Terminal

Baud Rate

The baud rate of the Remote I/O link
determines the maximum cable length.

57.6K

10,000 feet

115.2K

5,000 feet

230.4K

2,500 feet

Last Chassis

Specifies whether the terminal occupies
the last module group (no higher module
groups assigned) within the rack.

Yes, No