Software Error and Warning Messages

D–6

Publication 2711-6.0

Message

What to do

Meaning

Range minimum must be less than range
maximum.

Minimum value entered is greater than the
maximum value.

Enter a minimum value that’s less than the
maximum value.

Required network node not found.

The PanelView terminal is attempting to read
or write to a nonexistent location.

Check the SLC setup and program.

Saved device data is missing or corrupted
and cannot be used to update the tag
database.

A .PVA file was uploaded without project
device data.

Recreate all application device data.

Saved tag data is missing or corrupted and
cannot be used to update the tag database.

A .PVA file was uploaded without project tags.

Recreate all application tags.

Screen number already exists.
Please select another number.

Same screen number can’t be used for more
than one screen.

Assign a unique number (1-29,999) to screen.

Seek error:
(file name)

Internal error detected. Cause could be a
faulty disk drive or floppy disk.

Try again.

Selected global object on screen. Global
object can only appear once on each screen.

Global device already appears on the screen.

A global device can only appear once per
screen. Use a local device if needed.

Selected name in use. Enter another name.

Selected graphic image name that’s in use.

Select a different graphic image.

Source file not found or cannot be opened.

Incorrect file name or path.

Verify file name and path are correct. Retry.

Tag in application being opened that does not
exist in the Project.

The application contains one or more tags
that don’t exist in the associated project.

You are asked if you want to add the tag(s).

Tag information saved with application is
incomplete. Please check tag information
when application is opened.

Tag information is incomplete. Tag was
created but doesn’t contain all the necessary
information.

Supply missing tag data in the tag editor.

Tag must be scanned with scan group.

The tags associated with a particular alarm
are not in the same scan group.

Change the tag addresses for the alarm and
make sure they are in the same scan group.

Target terminal cannot support an alarm
banner.

The specified terminal does not support
alarms.

Change the terminal type or remove alarms,
alarm triggers, alarm buttons, and alarm
banners from the application.

Target terminal cannot support alarm triggers.

The specified terminal does not support
alarms.

Change the terminal type or remove alarms,
alarm triggers, alarm buttons, and alarm
banners from the application.

Target terminal cannot support alarms.

The specified terminal does not support
alarms.

Change the terminal type or remove alarms,
alarm triggers, alarm buttons, and alarm
banners from the application.

Target terminal cannot support ASCII callouts.

The specified terminal type does not support
ASCII callouts.

Use the Application Text editor to remove all
ASCII callouts from the messages.

Target terminal cannot support number of
alarms contained in the application.

The specified terminal type cannot support
the number of alarms contained in the
application.

Refer to the user manual to determine the
maximum number of alarms allowed.
Remove any unnecessary alarms.

Target terminal cannot support print only
objects.

The specified terminal type does not support
printing.

Remove all Print Only Objects from the
application.

Temporary file open failed: \ (file name)

PanelBuilder was unable to open a temporary
file during an upload. Probable cause is full
disk or write protect condition.

Check available disk space or write
protection.

Temporary file read failed: \ (file name)

PanelBuilder was unable to read the
temporary file. The file may be locked by
another application or corrupt.

Check if file is locked by another application.
If not, contact Allen-Bradley technical support.

Terminal and computer nodes cannot have
same value.

The terminal and personal computer can’t
have the same address for a DH485 transfer.

Make sure the terminal node address and
computer node address are different.

The existing alarm banner will be overwritten.
Do you wish to continue?

Pasting an alarm banner will overwrite any
existing banner.

Specify whether you want to continue or
cancel the operation.