Terminal and Communication Setup

Publication 2711-6.0

The PLC/SLC uses control tags to display specific screens and to
control the time/date on the PanelView terminal. The time and date
are updated every minute. The screen that the controller selects will
override the current PanelView screen and take the operator to the
current screen for that state of the operation.

To create or edit control tags:

1. Select the Control Tags tab in the Terminal Setup dialog.

2. Enter or select tag names for one or more control options. The

table below defines each option.

To clear a tag name field, highlight the text and press

DELETE

.

3. Click the Edit Tag button to edit the definition of a tag name or

edit the definition later using the Tag Editor.

4. Click OK to save the settings and exit the dialog.

Terminal

Control Tags

Description

Valid

Data Types

Screen
Number

Name of tag address where the controller writes a screen
number to control a screen change.
For operator controlled screen changes, the Screen Number
tag address must contain a 0.

Unsigned Integer

Date

Names of tag addresses where the controller writes the current
year, month and day for date displays.
The value at the Year tag address must be 2 digits (90–99 for
1990–1999 or 00–89 for 2000–2089).

To maintain Y2 compliance, the ladder logic must perform the
following conversions before sending the value to the terminal:
– If the year is

 1999, subtract 1900

– If the year is > 1999, subtract 2000

Unsigned Integer

Time

Names of tag addresses where the controller writes the current
hour, minutes and seconds for time displays.

Unsigned Integer

Defining PLC/SLC
Control Tags