2. From the Available Drivers List, click the desired driver by
double-clicking it or by clicking it and then clicking Add New.
The configuration dialog for the selected driver opens.
DF1 Driver
DF1 parameters for a PanelView
terminal must be set to:
Baud: 19200
Parity: None
Error Detect: CRC
Stop Bits: 1
Protocol: Full Duplex
Serial COM port on computer
Automatically detects the settings of the
DF1 driver on the serial COM port (when
connected to a PanelView terminal).
Device Type of
DF1 driver on computer
Default name
given to driver
1747-PIC Driver
Default name
assigned to driver
Station address
of computer is
typically 0.
Serial COM port on computer
3. Edit the driver parameters and click OK.
The driver appears in the Configured Drivers list. Click Close to
exit the Configure Devices dialog.