Terminal fm/am signal selection, Memobus/modbus termination, Table 3.14 – Yaskawa AC Drive Z1000 User Manual

Page 101: 10 control i/o connections

Advertising
background image

Table 3.14 Parameters H3-01 and H3-09 Details

No.

Parameter Name

Description

Setting

Range

Default

Setting

H3-01

Terminal A1 signal level selection

Selects the signal level for terminal A1.

0: 0 to 10 V with Zero Limit

1: 0 to 10 V without Zero Limit

2: 4 to 20 mA Current Input

3: 0 to 20 mA Current Input

0 to 3

0

H3-09

Terminal A2 signal level selection

Selects the signal level for terminal A2.

0: 0 to 10 V with Zero Limit

1: 0 to 10 V without Zero Limit

2: 4 to 20 mA Current Input

3: 0 to 20 mA Current Input

0 to 3

0

u

Terminal FM/AM Signal Selection

The signal type for terminals FM and AM can be set to either voltage or current output using jumper S5 on the terminal board

as explained in

Table 3.15

. When changing the setting of jumper S5, parameters H4-07 and H4-08 must be set accordingly.

The default selection is voltage output for both terminals.

Table 3.15 Jumper S5 Settings

Terminal

Voltage Output

Current Output

Terminal FM

AM

FM

V

I

AM

FM

V

I

Terminal AM

AM

FM

V

I

AM

FM

V

I

Table 3.16 Parameter H4-07 and H4-08 Details

No.

Parameter Name

Description

Setting

Range

Default

Setting

H4-07

Terminal FM signal level selection

0: 0 to 10 Vdc

2: 4 to 20 mA

0, 2

0

H4-08

Terminal AM signal level selection

u

MEMOBUS/Modbus Termination

This drive is equipped with a built-in termination resistor for the RS-422/RS-485 communication connector. DIP switch S2

enables or disabled the termination resistor as shown in

Table 3.17

. The OFF position is the default. The termination resistor

should be placed to the ON position when the drive is the last in a series of slave drives.

Refer to Switches and Jumpers on

the Control Board on page 99

to locate switch S2.

Table 3.17 MEMOBUS/Modbus Termination Switch S2 Settings

S2 Position

Description

ON

Internal termination resistor ON

OFF

Internal termination resistor OFF (default setting)

3.10 Control I/O Connections

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual

101

3

Electrical Installation