Fine-tuning open loop vector control for pm motors – Yaskawa AC Drive Z1000 User Manual

Page 199

Advertising
background image

u

Fine-Tuning Open Loop Vector Control for PM Motors

Table 5.2 Parameters for Fine-Tuning Performance in OLV/PM

Problem

Parameter No.

Corrective Action

Default

Suggested

Setting

Undesirable motor

performance

Motor parameters

(E1-oo, E5-oo)

• Check the settings for base and maximum frequency in the

E1-oo parameters.

• Check E5-oo parameters and set motor data correctly. Do

not enter line-to-line data where single-phase data is required,

and vice versa.

• Perform Auto-Tuning.

-

-

Poor motor torque and

speed response

Load Inertia Ratio

(n8-55)

Adjust parameter n8-55 to meet the load inertia ratio of the

machine.

0

Close to the actual

load inertia ratio

Speed Feedback

Detection Gain (n8-45)

Increase the speed feedback detection gain (n8-45).

0.80

Increase in

increments of 0.05

Torque Compensation

(C4-01)

Enable torque compensation.

Note:

Setting this value too high can cause

overcompensation and motor oscillation.

0.00

1.00

Oscillation at start or the

motor stalls

Pull-In Current during

Accel/Decel (n8-51)

Increase the pull-in current in n8-51

50%

Increase in steps

of 5%

DC Injection Braking

Current (b2-02), DC

Injection Time at Start

(b2-03)

Use DC Injection Braking at start to align the rotor. This may

cause a short reverse rotation at start.

b2-02 = 50%

b2-03 = 0.00 s

b2-03 = 0.5 s

Increase b2-02 if

needed

Load Inertia Ratio

(n8-55)

Increase the load inertia ratio.

Note:

Setting this value too high can cause

overcompensation and motor oscillation.

0

Close to the actual

load inertia ratio

Stalling or oscillation

occur when load is

applied during constant

speed

Pull-In Current

Compensation Time

Constant (n8-47)

Reduce n8-47 if hunting occurs during constant speed

5.0 s

Reduce in

increments

of 0.2 s

Pull-In Current (n8-48)

Increase the pull-in current in n8-48.

30%

Increase in

increments of 5%

Load Inertia Ratio

(n8-55)

Increase the load inertia ratio.

0

Close to the actual

load inertia ratio

Hunting or oscillation

occur

Speed feedback

Detection Gain (n8-45)

Reduce the speed feedback detection gain in n8-45.

0.80

Increase in

increments 0.05

STo fault trips when the

load is not excessively

high

Induced Voltage

Constant

(E5-09 or E5-24)

• Check and adjust the induced voltage constant.
• Check the motor nameplate and the data sheet or contact the

motor manufacturer.

Depends on

drive

capacity

Refer to the motor

data sheet or the

nameplate.

Stalling or STo occurs at

high speed as the output

voltage becomes

saturated

Output Voltage Limit

(n8-62)

Set the value of the input voltage to parameter n8-62

200 Vac

(200 V class)

400 Vac

(400 V class)

Set equal to input

voltage

5.2 Motor Performance Fine-Tuning

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual

199

5

Troubleshooting