L4: speed detection, L5: fault restart – Yaskawa AC Drive Z1000 User Manual

Page 312

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L3-26

(455)

Additional DC Bus

Capacitors

ExtDC busCapSize

When DC bus capacitors have been added externally, be sure

to add those values to the internal capacitor table for proper DC

bus calculations.

Default: 0 μF

Min: 0

Max: 65000

L3-27

(456)

Stall Prevention

Detection Time

Stl Prev DetTime

Sets the time the current must exceed the Stall Prevention level

to activate Stall Prevention.

Default: 50 ms

Min.: 0

Max.: 5000

<1> Upper limit is dependent on parameter L8-38, Frequency Reduction Selection.
<2> The setting range is 0 to 2 in OLV/PM control mode.
<3> Default setting is dependent on parameter E1-01, Input voltage Setting.
<4> Values shown are specific to 200 V class drives. Double the value for 400 V class drives.
<5> Default setting is determined by parameter A1-02, Control Mode Setting.
<6> Parameter value changes automatically if E2-11 is manually changed or changed by Auto-Tuning.
<7> Default setting is dependent on parameter o2-04, Drive Model Selection.

u

L4: Speed Detection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L4-01

(499)

Speed Agreement

Detection Level

Spd Agree Level

L4-01 sets the frequency detection level for digital output

functions H2-oo = 2, 3, 4, 5.

Default: 0.0 Hz

Min.: 0.0

Max.: 240.0

L4-02

(49A)

Speed Agreement

Detection Width

Spd Agree Width

L4-02 sets the hysteresis or allowable margin for speed

detection.

Default:2.0 Hz

Min.: 0.0

Max.: 20.0

L4-03

(49B)

Speed Agreement

Detection Level (+/-) Spd Agree Lvl+-

L4-03 sets the frequency detection level for digital output

functions H2-oo = 13, 14, 15, 16.

Default: 0.0 Hz

Min.: -240.0

Max.: 240.0

L4-04

(49C)

Speed Agreement

Detection Width

(+/-)

Spd Agree Wdth+-

L4-04 sets the hysteresis or allowable margin for speed

detection.

Default: 2.0 kHz

Min.: 0.0

Max.: 20.0

L4-05

(49D)

Frequency Reference

Loss Detection

Selection

Ref Loss Sel

0: Stop

1: Run@L4-06PrevRef

0: Stop. Drive stops when the frequency reference is lost.

1: Run. Drive runs at a reduced speed when the frequency

reference is lost.

Default: 1

Range: 0, 1

138

L4-06

(4C2)

Frequency Reference

at Reference Loss

Fref at Floss

Sets the percentage of the frequency reference that the drive

should run with when the frequency reference is lost.

Default: 80.0%

Min.: 0.0

Max.: 100.0

138

L4-07

(470)

Speed Agreement

Detection Selection

Freq Detect Sel

0: No Detection @BB

1: Always Detected

0: No detection during baseblock.

1: Detection always enabled.

Default: 0

Range: 0, 1

u

L5: Fault Restart

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L5-01

(49E)

Number of Auto Restart

Attempts

Num of Restarts

Sets the number of times the drive may attempt to restart after

the following faults occur: GF, LF, oC, ov, PF, oL1, oL2, oL3,

STo, Uv1.

Default: 0

Min.: 0

Max.: 10

139

L5-02

(49F)

Auto Restart Fault

Output Operation

Selection

Restart Sel

0: Flt Outp Disabld

1: Flt Outp Enabled

0: Fault output not active.

1: Fault output active during restart attempt.

Default: 0

Range: 0, 1

179

L5-03

(4A0)

Time to Continue

Making Fault Restarts

Max Restart Time

Enabled only when L5-05 is set to 0. Causes a fault if a fault

restart cannot occur after the set time passes.

Default: 180.0 s

Min.: 0.0

Max.: 600.0

139

L5-04

(46C)

Fault Reset Interval

Time

Flt Reset Wait T

Sets the amount of time to wait between performing fault

restarts.

Default: 10.0 s

Min.: 0.5

Max.: 600.0

179

B.8 L: Protection Function

312

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual