Settings for N.C. and N.O. input for the following

functions were selected simultaneously:
• External Search Command 1 and External

Search Command 2 (61 vs. 62)

• Fast Stop N.O. and Fast Stop N.C. (15 vs. 17)
• KEB for Momentary Power Loss and High Slip

Braking

(65, 66, 7A, 7B vs. 68)

• KEB Command 1 and KEB Command 2 (65, 66

vs. 7A, 7B)

• FWD Run Command (or REV) and FWD/REV

Run Command (2-wire) (40, 41 vs. 42, 43)

• Drive Enable (60 vs. 6A)

• Check if contradictory settings have simultaneously been assigned to the multi-function input

terminals.

• Correct setting errors.

One of the following settings was entered while

H1-oo = 2 (External Reference 1/2):
• b1-15 = 4 (Pulse Train Input) but the pulse train

input selection is not set for the frequency

reference (H6-01 > 0)

• b1-15 or b1-16 set to 3 but no option card is

connected

• Although b1-15 = 1 (Analog Input) and H3-02

or H3-10 are set to 0 (Frequency Bias)

Correct the settings for the multi-function input terminal parameters.

H2-oo is set to 38 (Drive Enabled) and H1-oo

is not set to 6A (Drive Enable)

HOA Keypad Display

Error Name

oPE05

Run Command/Frequency Reference Source Selection Error

Cause

Possible Solutions

Frequency reference is assigned to an option card

(b1-01 = 3) and an input option card is not

connected to the drive

Reconnect the input option card to the drive.

The Run command is assigned to an option card

(b1-02 = 3) and an input option card is not

connected to the drive

HOA Keypad Display

Error Name

oPE07

Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function analog inputs H3-02 or H3-10 and PI functions

conflict.

Cause

Possible Solutions

At least two analog input terminals are set to the

same function (i.e., at least two of these parameters

have the same setting: H3-02 or H3-10)

Change the settings to H3-02 and H3-10 so that functions no longer conflict.

Note:

Both 0 (Frequency Reference Bias) and F (Not Used) can be set to H3-02 and H3-10

simultaneously.

The following simultaneous contradictory

settings:

H3-02 or H3-10 = C (PI Target Value) while

b5-18 = 1 (enables b5-19 as the target PI value)

Disable one of the PI selections.

HOA Keypad Display

Error Name

oPE08

Parameter Selection Error
A function has been set that cannot be used in the motor control method selected.

Cause

Possible Solutions

In OLV/PM, parameters E5-02 to E5-07 are set to

0

When using a special-purpose motor, set E5-oo in accordance with the test report provided.

The following settings have occurred in OLV/PM:
• E5-03 does not equal 0
• E5-09 and E5-24 are both equal to 0, or neither

equals 0

• Set E5-09 or E5-24 to the correct value, and set the other to 0.
• Set the motor rated current for PM to 0 (E5-03).

Note:

Use U1-18 to find parameters that are set outside the specified setting range. When multiple errors occur simultaneously, other errors are

given precedence over oPE08.

5.6 Programming Errors

226