Refer to, For a list of alarm codes, Minor faults and alarms – Yaskawa AC Drive Z1000 User Manual

Page 203: Operation errors

Advertising
background image

n

Minor Faults and Alarms

Refer to

Table 5.6

for an overview of possible alarm codes. Conditions such as overvoltages can trip faults and alarms. It is

important to distinguish between faults and alarms to determine the proper corrective actions.
When the drive detects an alarm, the ALM indicator LED blinks and the alarm code display flashes. Most alarms trigger a

digital output programmed for alarm output (H2-oo = 10). A fault (not an alarm) is present if the ALM LED lights without

blinking.

Refer to Faults on page 202

for information on fault codes.

Table 5.6 Minor Fault and Alarm Displays

HOA

Keypad

Display

Name

Minor Fault

Output

(H2-oo = 10)

Page

bAT

HOA Keypad Battery Voltage Low

YES

205

bb

Drive Baseblock

No output

218

bUS

Option Card Communications Error

YES

218

CALL

Serial Communication Transmission

Error

YES

218

CE

MEMOBUS/Modbus Communication

Error

YES

218

CrST

Cannot Reset

YES

219

dnE

Drive Disabled

YES

219

EF

Run Command Input Error

YES

219

EF0

Option Card External Fault

YES

219

EF1 to

EF7

External Fault

(input terminal S1 to S7)

YES

220

FAn

Internal Fan Fault

YES

207

FbH

Excessive PI Feedback

YES

220

FbL

PI Feedback Loss

YES

220

Fn1

External Fan Fault

YES

208

inTLK

<1>

Interlock Open

No output

221

LT-1

Cooling Fan Maintenance Time

No output

<2>

221

HOA

Keypad

Display

Name

Minor Fault

Output

(H2-oo = 10)

Page

LT-2

Capacitor Maintenance Time

No output

<2>

221

LT-3

Soft Charge Bypass Relay Maintenance

Time

No output

<2>

221

oH

Heatsink Overheat

YES

221

oH2

Drive Overheat

YES

222

oH3

Motor Overheat

YES

222

oL3

Overtorque 1

YES

222

ov

Overvoltage

YES

222

PASS

MEMOBUS/Modbus Test Mode

Complete

No output

223

SAFE

Customer Safety

No output

223

SE

MEMOBUS/Modbus Test Mode Fault

YES

223

TdE

Thermistor Disconnect

YES

223

TIM

Time Not Set

YES

215

UL3

Undertorque 1

YES

223

UL6

Undertorque 6

YES

223

Uv

Undervoltage

YES

223

voF

Output Voltage Detection Fault

YES

224

WrUn

Waiting for Run

YES

224

<1> ALM LED will not blink.
<2> Output when H2-oo = 2F.

n

Operation Errors

Table 5.7 Operation Error Displays

HOA

Keypad

Display

Name

Page

oPE01

Drive Unit Setting Error

225

oPE02

Parameter Setting Range Error

225

oPE03

Multi-Function Input Setting Error

225

oPE05

Run Command Selection Error

226

oPE07

Multi-Function Analog Input Selection Error

226

oPE08

Parameter Selection Error

226

HOA

Keypad

Display

Name

Page

oPE09

PI Control Selection Error

227

oPE10

V/f Data Setting Error

227

oPE11

Carrier Frequency Setting Error

227

oPE16

Energy Saving Constants Error

227

oPE27

BP Program Error

228

oPE28

Sequence Timer Error

228

5.3 Drive Alarms, Faults, and Errors

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual

203

5

Troubleshooting

Advertising