No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L8-06

(4B2)

Input Phase Detection

Level

Inp Ph Loss Lvl

When ripple is observed in the DC bus, expansion of the input

bias is calculated. This value becomes the input phase if the

difference between the maximum and minimum values of the

ripple is greater than the value set to L8-06.
Detection Level = 100% = Voltage class x

Default:

<1>

Min.: 0.0%

Max.: 50.0%

181

L8-07

(4B3)

Output Phase Loss

Protection Selection

Outp Ph Loss Det

0: Disabled

1: 1PH Loss Det

2: 2/3PH Loss Det

0: Disabled

1: Enabled (triggered by a single phase loss)

2: Enabled (triggered when two phases are lost)

Default: 1

Range: 0 to 2

182

L8-09

(4B5)

Output Ground Fault

Detection Selection

Grnd Flt Det Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default:

<1>

Range: 0, 1

182

L8-10

(4B6)

Heatsink Cooling Fan

Operation Selection

Fan On/Off Sel

0: Dur Run (OffDly)

1: Always On

0: During run only. Fan operates only during run for L8-11

seconds after stop.

1: Fan always on. Cooling fan operates whenever the drive is

powered up.

Default: 0

Range: 0, 1

182

L8-11

(4B7)

Heatsink Cooling Fan

Off Delay Time

Fan Delay Time

Sets a delay time to shut off the cooling fan after the Run

command is removed when L8-10 = 0.

Default: 300 s

Min.: 0

Max.: 300

182

L8-12

(4B8)

Ambient Temperature

Setting

Ambient Temp

Enter the ambient temperature. This value adjusts the oL2

detection level.

Default: 40 °C

Min.: 40

Max.: 60

182

L8-15

(4BB)

oL2 Characteristics

Selection at Low Speeds

OL2 Sel @ L-Spd

0: Disabled

1: Enabled

0: No oL2 level reduction below 6 Hz.

1: oL2 level is reduced linearly below 6 Hz. It is halved at 0 Hz. Default: 1

Range: 0, 1

183

L8-18

(4BE)

Software Current Limit

Selection

Soft CLA Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

183

L8-19

(4BF)

Frequency Reduction

Rate during Overheat

Pre-Alarm

Fc Red dur OHAlm

Specifies the frequency reference reduction gain at overheat

pre-alarm when L8-03 = 4.

Default: 20.0%

Min.: 0.0

Max.: 100.0

183

L8-27

(4DD)

Overcurrent Detection

Gain

OC Level

Sets the gain for overcurrent detection as a percentage of the

motor rated current. Overcurrent is detected using the lower

value between the overcurrent level of the drive or the value set

to L8-27.

Default: 300.0%

Min.: 0.0

Max.: 300.0

183

L8-29

(4DF)

Current Unbalance

Detection (LF2)

LF2 Flt Det Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default: 1

Range: 0, 1

183

L8-32

(4E2)

Main Contactor and

Cooling Fan Power

Supply Failure Selection

MC/FAN PS FltSel

0: Ramp to stop

1: Coast to stop

2: Fast-Stop

3: Alarm only

4: Run@L8-19 Rate

Determines drive response when a fault occurs with the internal

cooling fan.

0: Ramp to stop

1: Coast to stop

2: Fast stop (Decelerate to stop using the deceleration time set

to C1-09)

3: Alarm only (“FAn” will flash)

4: Continue operation at reduced speed as set to L8-19.

Default: 1

Range: 0 to 4

184

L8-35

(4EC)

Installation Method

Selection

Installation Sel

0: IP00/OpenChassis

2: IP20/Nema Type 1

3: ExternalHeatsink

0: IP00/Open-Chassis enclosure

2: IP20/NEMA Type 1 enclosure

3: External Heatsink Installation

Default:

<1> <2>

<3>

Range: 0, 2, 3

184

L8-38

(4EF)

Carrier Frequency

Reduction

Fc Reduct dur OL

0: Disabled

1: Active below 6Hz

2: Active @ any Spd

0: Disabled

1: Enabled below 6 Hz

2: Enabled for the entire speed range

Default:

<4>

Range: 0 to 2

184

L8-40

(4F1)

Carrier Frequency

Reduction Off Delay

Time

Fc Reduct Time

Sets the time that the drive continues running with reduced

carrier frequency after the carrier reduction condition is gone.

Setting 0.00 s disables the carrier frequency reduction time.

Default: 0.50 s

Min.: 0.00

Max.: 2.00

185

L8-41

(4F2)

High Current Alarm

Selection

High Cur Alm Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled.

An alarm is triggered at output currents above 150% of drive

rated current.

Default: 0

Range: 0, 1

185

L8-97

(3104)

Carrier Frequency

Reduction Selection

during oH Pre-Alarm

FC Sel dur OHAlm

0: Disabled

1: Enabled

Carrier frequency reduction protection selection. It is reduced

to the carrier frequency at oH pre-alarm.

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

B.8 L: Protection Function

314