D.3 UL/cUL Standards

u

UL Standards Compliance

The UL/cUL mark applies to products in the United States and Canada. It indicates that UL has performed product testing and

evaluation, and determined that their stringent standards for product safety have been met. For a product to receive UL

certification, all components inside that product must also receive UL certification.

Figure D.7 UL/cUL Mark

This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The conditions described

below must be met to maintain compliance when using this drive in combination with other equipment:

n

Installation Area

Do not install the drive to an area greater than pollution degree 2 (UL standard).

n

Ambient Temperature

IP20/NEMA Type 1 Enclosure, External Heatsink (2A0011 to 2A0073 and 4A0005 to 4A0302): -10 to +40 °C (14 to 104 °F)
IP00/Open Type Enclosure (2A0343 and 2A0396 and 4A0361 to 4A0590): -10 to +50 °C (14 to 122 °F)

n

Main Circuit Terminal Wiring

Yaskawa recommends using closed-loop crimp terminals on all drive models. To maintain UL/cUL approval, UL Listed

closed-loop crimp terminals are specifically required when wiring the drive main circuit terminals on models 2A0031 to

2A0396 and 4A0034 to 4A0590. Use only the tools recommended by the terminal manufacturer for crimping.

Refer to Closed-

Loop Crimp Terminal Size on page 368

for closed-loop crimp terminal recommendations.

The wire gauges listed in the following tables are Yaskawa recommendations. Refer to NEC table 310-16 for proper wire

gauge selection for terminals -M, +M, -1, +3, and ground.

Wire Gauges and Tightening Torques

Refer to Wire Gauges and Tightening Torque on page 83

to select the appropriate wires and crimp terminals for use in the

United States.

Note:

The mark indicates the terminals for protective ground connection as defined in IEC/EN 60417-5019.

Grounding impedance:

200 V: 100 Ω or less

400 V: 10 Ω or less

Closed-Loop Crimp Terminal Recommendations

Yaskawa recommends using closed-loop crimp terminals on all drive models. To maintain UL/cUL approval, UL Listed

closed-loop crimp terminals are specifically required when wiring the drive main circuit terminals on models 2A0031 to

2A0396 and 4A0034 to 4A0590. Use only the tools recommended by the terminal manufacturer for crimping. Yaskawa

recommends crimp terminals made by JST and Tokyo DIP (or equivalent) for the insulation cap.

Table D.3

matches the wire gauges and terminal screw sizes with Yaskawa-recommended crimp terminals, tools, and insulation

caps. Refer to the appropriate Wire Gauge and Torque Specifications table for the wire gauge and screw size for your drive

model. Place orders with a Yaskawa representative or the Yaskawa sales department. Refer to local codes for proper selections.

Table D.3 Closed-Loop Crimp Terminal Size

Wire Gauge

Terminal

Screws

Crimp Terminal

Model Number

Tool

Insulation

Cap

Model No.

Code

<1>

Machine No.

Die Jaw

2 mm

2

14 AWG

M4

R2-4

YA-4

AD-900

TP-003

100-054-028

3.5 / 5.5 mm

2

12 / 10 AWG

M4

5.5-4NS

YA-4

AD-900

TP-005

100-064-248

D.3 UL/cUL Standards

368