7 basic drive setup adjustments – Yaskawa AC Drive Z1000 User Manual

Page 132

Advertising
background image

n

C1-01 to C1-04: Accel, Decel Times 1 and 2

Four different sets of acceleration and deceleration times can be set in the drive by digital inputs, motor selection, or switched

automatically.
Acceleration time parameters always set the time to accelerate from 0 Hz to the maximum output frequency (E1-04).

Deceleration time parameters always set the time to decelerate from maximum output frequency to 0 Hz. C1-01 and C1-02

are the default active accel/decel settings.

No.

Parameter Name

Setting Range

Default

C1-01

Acceleration Time 1

0.1 to 6000.0 s

30.0 s

C1-02

Deceleration Time 1

C1-03

Acceleration Time 2

C1-04

Deceleration Time 2

Switching Acceleration Times by Digital Input

Accel/decel times 1 are active by default if no input is set.

Table 4.17 Accel/Decel Time Selection by Digital Input

Accel/Decel Time Sel. 1

H1-oo = 7

Active Times

Acceleration

Deceleration

0

C1-01

C1-02

1

C1-03

C1-04

Figure 4.19

shows an operation example for changing accel/decel. times. The example below requires that the stopping method

be set for “Ramp to stop” (b1-03 = 0).

Output

frequency

Accel Time 1

(C1-01)

Decel Time 1

(C1-02)

Accel Time 2

(C1-03)

Decel Time 2

(C1-04)

Decel Time 1

(C1-02)

FWD (REV)

Run command

ON

OFF

ON

ON

Accel/Decel Time Selection 1

(Terminals S1 to S7, H1-oo = “7”)

Figure 4.19 Timing Diagram of Accel/Decel Time Change

Switching Accel/Decel Times by a Frequency Level

The drive can switch between different acceleration and deceleration times automatically. The drive will switch from accel/

decel time 2 in C1-03 and C1-04 to the default accel/decel time in C1-01 and C1-02 when the output frequency exceeds the

frequency level set in parameter C1-11. When the frequency falls below this level, the accel/decel times are switched back.

Figure 4.20

shows an operation example.

Note:

Acceleration and deceleration times selected by digital inputs have priority over the automatic switching by the frequency level set to C1-11.

For example, if accel/decel time 2 is selected, the drive will use only accel/decel time 2; it will not switch from accel/decel time 2 to the

selected time.

Output Frequency

C1-11

Accel/Decel Time

Switch Frequency

C1-03

setting

When the output frequency C1-11, drive uses Accel/Decel Time 1 (C1-01, -02)
When the output frequency < C1-11, drive uses Accel/Decel Time 2 (C1-03, -04)

C1-01

setting

C1-02

setting

C1-04

setting

Figure 4.20 Accel/Decel Time Switching Frequency

4.7 Basic Drive Setup Adjustments

132

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual

Advertising