L2: Momentary Power Loss Ride-Thru

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L2-01

(485)

Momentary Power Loss

Operation Selection

PwrL Selection

0: Disabled

1: Enbl with Timer

2: Enbl whl CPU act

0: Disabled.

Drive trips on Uv1 fault when power is lost.

1: Recover within the time set in L2-02.

Uv1 will be detected if power loss is longer than L2-02.

2: Recover as long as CPU has power.

Uv1 is not detected.

Default: 0

Range: 0 to 2

137

L2-02

(486)

Momentary Power Loss

Ride-Thru Time

PwrL Ridethru t

Sets the Power Loss Ride-Thru time. Enabled only when

L2-01 = 1 or 3.

Default:

<1>

Min.: 0.0 s

Max.: 25.5 s

138

L2-03

(487)

Momentary Power Loss

Minimum Baseblock

Time

PwrL Baseblock t

Sets the minimum wait time for residual motor voltage decay

before the drive output reenergizes after performing Power

Loss Ride-Thru.

Increasing the time set to L2-03 may help if overcurrent or

overvoltage occur during Speed Search or during DC Injection

Braking.

Default:

<1>

Min.: 0.1 s

Max.: 5.0 s

L2-04

(488)

Momentary Power Loss

Voltage Recovery Ramp

Time

PwrL V/F Ramp t

Sets the time for the output voltage to return to the preset V/f

pattern during Speed Search.

Default:

<1>

Min.: 0.0 s

Max.: 5.0 s

L2-05

(489)

Undervoltage Detection

Level (Uv1)

PUV Det Level

Sets the DC bus undervoltage trip level.

Default: 190 Vdc

<2> <3>

Min.: 150 Vdc
Max.: 220 Vdc

<3>

L2-06

(48A)

KEB Deceleration

Time

KEB Decel Time

Sets the time required to decelerate from the speed when KEB

was activated to zero speed.

Default: 0.00 s

Min.: 0.00

Max.: 6000.0

L2-07

(48B)

KEB Acceleration

Time

KEB Accel Time

Sets the time to accelerate to the frequency reference when

momentary power loss is over. If set to 0.0, the active

acceleration time is used.

Default: 0.00 s

Min.: 0.00

Max.: 6000.0

L2-08

(48C)

Frequency Gain at KEB

Start

KEB Freq Red

Sets the percentage of output frequency reduction at the

beginning of deceleration when the KEB Ride-Thru function is

started.

Reduction = (slip frequency before KEB) × L2-08 × 2

Default: 100%

Min.: 0

Max.: 300

L2-10

(48E)

KEB Detection Time

(Minimum KEB Time) KEB Detect Time

Sets the time to perform KEB Ride-Thru.

Default: 50 ms

Min.: 0

Max.: 2000

L2-11

(461)

DC Bus Voltage

Setpoint during KEB

KEB DC Bus Level

Sets the desired value of the DC bus voltage during KEB Ride-

Thru.

Default:

<2>

[E1-01] × 1.22

Min.: 150 Vdc
Max.: 400 Vdc

<3>

L2-29

(475)

KEB Method Selection

KEB Mode Sel

0: Single Mode KEB1

1: Single Mode KEB2

0: Single Drive KEB Ride-Thru 1

1: Single Drive KEB Ride-Thru 2

Default: 0

Range: 0, 1

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Default setting is dependent on parameter E1-01, Input voltage Setting.
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives.

B.8 L: Protection Function