Model

Terminal

Recomm. Gauge

AWG, kcmil

Wire Range

AWG, kcmil

Screw

Size

Tightening Torque

N·m (lb.in.)

4A0156

<1>

R/L1, S/L2, T/L3

3 × 2

1/0 to 3/0

M8

13.5 to 15.0

(120 to 133)

U/T1, V/T2, W/T3

3 × 2

-M, +M

4A0180

<1>

R/L1, S/L2, T/L3

2 × 2

1/0 to 3/0

M8

13.5 to 15.0

(120 to 133)

U/T1, V/T2, W/T3

2 × 2

-M, +M

4A0240

<1>

R/L1, S/L2, T/L3

1/0 × 2

1/0 to 3/0

M8

13.5 to 15.0

(120 to 133)

U/T1, V/T2, W/T3

1/0 × 2

-M, +M

4A0302

<1>

R/L1, S/L2, T/L3

3/0 × 2

1/0 to 4/0

M10

27.0 to 30.0

(239 to 266)

U/T1, V/T2, W/T3

3/0 × 2

-M, +M

4A0361

<1>

R/L1, S/L2, T/L3

4/0 × 2

3/0 to 600

M12

32.0 to 40.0

(283 to 354)

U/T1, V/T2, W/T3

4/0 × 2

3/0 to 600

–, +1

4/0 to 600

+3

3/0 to 600

M10

18 to 23

(159 to 204)

1

1 to 350

M12

32 to 40

(283 to 354)

4A0414

<1>

R/L1, S/L2, T/L3

300 × 2

4/0 to 300

M12

32.0 to 40.0

(283 to 354)

U/T1, V/T2, W/T3

300 × 2

4/0 to 300

–, +1

3/0 to 300

+3

3/0 to 300

1

1 to 3/0

4A0480

<1>

R/L1, S/L2, T/L3

1/0 × 4

3/0 to 300

M12

32.0 to 40.0

(283 to 354)

U/T1, V/T2, W/T3

1/0 × 4

–, +1

+3

4A0590

<1>

R/L1, S/L2, T/L3

3/0 × 4

3/0 to 300

M12

32.0 to 40.0

(283 to 354)

U/T1, V/T2, W/T3

3/0 × 4

–, +1

+3

<1> Drive models 4A0034 to 4A0590 require the use of closed-loop crimp terminals for UL/cUL compliance. Use only the tools recommended by the

terminal manufacturer for crimping.

u

Main Circuit Terminal and Motor Wiring

This section outlines the various steps, precautions, and checkpoints for wiring the main circuit terminals and motor terminals.

WARNING! Electrical Shock Hazard. Do not connect the AC power line to the output terminals of the drive. Failure to comply could result

in death or serious injury by fire as a result of drive damage from line voltage application to output terminals.

NOTICE: When connecting the motor to the drive output terminals U/T1, V/T2, and W/T3, the phase order for the drive and motor should

match. Failure to comply with proper wiring practices may cause the motor to run in reverse if the phase order is backward.

NOTICE: Route motor leads U/T1, V/T2, and W/T3 separate from all other leads to reduce possible interference related issues. Failure to

comply may result in abnormal operation of drive and nearby equipment.

NOTICE: Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits. Failure to comply could result in damage

to the drive, phase-advancing capacitors, LC/RC noise filters or ground fault circuit interrupters.

3.8 Main Circuit Wiring