Yaskawa AC Drive Z1000 User Manual

Page 228

Advertising
background image

HOA Keypad Display

Error Name

oPE27

BP Program Error
Bypass mode is not correctly configured.

Cause

Possible Solutions

If digital inputs A4, A5, or A7 or digital outputs

A4 or A5 are programmed, then all must be

programmed

Correct the parameter settings.

Digital inputs A4, A5, or A7 and digital outputs A4

or A5 are programmed and one of the following

conditions is true:
• H1-0o = 0 (3-Wire Sequence)
• L5-01 > 0 and S4-01 = 1 (Auto Transfer of Fault)
• H1-oo≤ A6 and H2-oo = A6
• H1-oo = A6 and H2-oo≤ A6

HOA Keypad Display

Error Name

oPE28

Sequence Timer Error
One or more of the sequence timers is not set in the correct order.

Cause

Possible Solutions

One of the following contradictory settings is true:
• S2-01 > S2-02
• S2-06 > S2-07
• S2-11 > S2-12
• S2-16 > S2-17

Correct the parameter settings.

5.6 Programming Errors

228

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual