Control mode selection, 2 general description – Yaskawa AC Drive Z1000 User Manual

Page 26

Advertising
background image

Motor Capacity kW (HP)

Three-Phase 400 V Class

Input Voltage < 460 V

Input Voltage ≥ 460 V

Model CIMR-Zo

Rated Output Current (A)

185 (250)

220 (300)

4A0361

361

<3>

220 (300)

260 (350)

4A0414

414

<3>

250 (340)

300 (400)

4A0480

480

<3>

300 (400)

370 (500)

4A0590

590

<3>

<1> Assumes the carrier frequency is set to 5 kHz.
<2> Assumes the carrier frequency is set to 4 kHz.
<3> Assumes the carrier frequency is set to 2 kHz.

Note:

Current derating is required when setting the carrier frequency higher.

u

Control Mode Selection

Table 1.2

gives an overview of the Z1000 control modes and the various features associated with those control modes.

Table 1.2 Control Modes and Features

Motor Type

Induction Motors

Permanent Magnet Motors

Comments

Control Mode

V/f

OLV/PM

Parameter Setting

A1-02 = 0

A1-02 = 5

Default Setting is V/f control (A1-02 = 0)

Basic Description

V/f control

Open Loop Vector control

for PM motors

Type of

Applications

Motor Type

IM

PM

Multi Motor

YES

Motor data unknown

YES

High Speed Accuracy

YES

Control

Characteristics

Speed Control Range

1:40

1:20

May fluctuate with characteristics and motor
temperature.

Speed Accuracy

±2 to 3%

±0.2%

Speed deviation when operating at constant speed
may fluctuate with characteristics and motor
temperature.

Speed Response

3 Hz (approx.)

10 Hz

Max. frequency of a speed reference signal that the
drive can follow may fluctuate with characteristics
and motor temperature.

Starting Torque

140% at 3 Hz

100% at

5% speed

Starting torque may fluctuate with characteristics and
motor temperature.
Performance may differ by capacity.

Application-

Specific

Auto-Tuning

• Energy Saving Tuning
• Line to line resistance

• Stationary
• Line to line resistance

Automatically adjusts parameter settings that concern
electrical characteristics of the motor.

Speed Search

YES

YES

Bi-directional speed detection of a coasting motor to
restart it without stopping.

Energy-Saving Control

YES

Saves energy by always operating the motor at its
maximum efficiency.

High Slip Braking

YES

Increases motor loss to allow for faster deceleration.
Effectiveness may vary based on motor
characteristics.

Kinetic Energy Buffering

YES

YES

Decelerates the drive to allow it to ride through a
momentary power loss and continue operation.

Overexcitation Deceleration

YES

Allows faster deceleration without overvoltage trip.

Overvoltage Suppression

YES

YES

Prevents overvoltage by increasing speed during
regeneration.

1.2 General Description

26

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual

Advertising