Yaskawa AC Drive Z1000 User Manual

Page 175

Advertising
background image

Setting 3: 0 to 20 mA Current Input

The input level is 0 to 20 mA. Negative input values by negative bias or gain settings are limited to 0%.

n

H3-02: Terminal A1 Function Selection

Selects the input signal level for analog input A1.

No.

Name

Setting Range

Default

H3-02

Terminal A1 Function Selection

0 to 41

0

n

H3-09: Terminal A2 Signal Level Selection

Selects the input signal level for analog input A2. Set Jumper S1 on the terminal board accordingly for a voltage input or

current input.

No.

Name

Setting Range

Default

H3-09

Terminal A2 Signal Level Selection

0 to 3

2

Setting 0: 0 to 10 V with Zero Limit

The input level is 0 to 10 Vdc. Negative input values will be limited to 0.

Refer to Setting 0: 0 to 10 V with Zero Limit on

page 174

.

Setting 1: 0 to 10 V without Zero Limit

The input level is 0 to 10 Vdc. Negative input values will be accepted.

Refer to Setting 1: 0 to 10 V without Zero Limit on

page 174

.

Setting 2: 4 to 20 mA Current Input

The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.

Setting 3: 0 to 20 mA Current Input

The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.

n

H3-10: Terminal A2 Function Selection

Determines the function assigned to analog input terminal A2.

No.

Name

Setting Range

Default

H3-10

Terminal A2 Function Selection

0 to 26

0

n

Multi-Function Analog Input Terminal Settings

See

Table 4.38

for information on how H3-02 and H3-10 determine functions for terminals A1 and A2.

Note:

The scaling of all input functions depends on the gain and bias settings for the analog inputs. Set these to appropriate values when selecting

and adjusting analog input functions.

Table 4.38 Multi-Function Analog Input Terminal Settings

Setting

Function

Page

0

Frequency Bias

175

1

Frequency Gain

176

2

Auxiliary Frequency Reference 1

176

3

Auxiliary Frequency Reference 2

176

4

Output Voltage Bias

5

Accel/Decel Time Gain

6

DC Injection Braking Current

7

Overtorque/Undertorque Detection Level

8

Stall Prevention Level During Run

Setting

Function

Page

9

Output Frequency Lower Limit Level

B

PI Feedback

176

C

PI Setpoint

176

D

Frequency Bias

176

E

Motor Temperature (PTC Input)

176

F

Through Mode

176

16

Differential PI Feedback

176

25

Secondary PI Setpoint

26

Secondary PI Feedback

Setting 0: Frequency Bias

The input value of an analog input set to this function will be added to the analog frequency reference value. When the frequency

reference is supplied by a different source other than the analog inputs, this function will have no effect. Use this setting also

when only one of the analog inputs is used to supply the frequency reference.
By default, analog inputs A1 and A2 are set for this function. Simultaneously using A1 and A2 increases the frequency reference

by the total of all inputs.

4.13 Advanced Drive Setup Adjustments

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual

175

4

Start-Up Programming & Operation