A.4 Drive Derating Data

The drive can be operated at above the rated temperature, altitude, and default carrier frequency by derating the drive capacity.

u

Carrier Frequency Derating

Derate the drive according to

Figure A.1

to

Figure A.5

as the carrier frequency increases above the factory default setting.

12.5 kHz

5 kHz

100%

60%

0

Figure A.1 Carrier Frequency Derating (2A0011 to 2A0114 and 4A0005 to 4A0096)

8 kHz

5 kHz

100%

80%

10 kHz

0

Figure A.2 Carrier Frequency Derating (2A0143 to 2A0273 and 4A0124 to 4A0180)

4kHz

100%

60%

10kHz

0

Figure A.3 Carrier Frequency Derating (4A0240 and 4A0302)

A.4 Drive Derating Data

276