Setting 1: Enabled for Output Frequencies below 6 Hz

The carrier frequency is reduced at speeds below 6 Hz when the current exceeds 100% of the drive rated current. The drive

returns to the normal carrier frequency when the current falls below 88% or the output frequency exceeds 7 Hz.

Setting 2: Enabled for Entire Frequency Range

The carrier frequency is reduced at the following speeds:
• Below 6 Hz when the current exceeds 100% of the drive rated current.
• Above 7 Hz when the current exceeds 112% of the drive rated current.
The drive uses the delay time set in parameter L8-40 and a hysteresis of 12% when switching the carrier frequency back to

the set value.

n

L8-40: Carrier Frequency Reduction Off-Delay Time

Sets a hold time before returning to the original carrier frequency setting after the carrier frequency has been temporarily

derated as determined by L8-38. The carrier frequency reduction function is disabled when this value is 0.00 s.

No.

Name

Setting Range

Default

L8-40

Carrier Frequency Reduction Off-Delay Time

0.00 to 2.00 s

0.50 s

n

L8-41: High Current Alarm Selection

Triggers a high current alarm (HCA) when the output current exceeds 150% of the drive rated current.

No.

Name

Setting Range

Default

L8-41

High Current Alarm Selection

0, 1

0

Setting 0: Disabled

No alarm is detected.

Setting 1: Enabled

An alarm is triggered when the output current exceeds 150% of the drive rated current. A digital output set for an alarm

(H2-oo = 10) will close.

n

o1-01: Drive Mode Unit Monitor Selection

The frequency reference display appears when the drive is powered up. Pressing the up arrow key will display the following

data: frequency reference → rotational direction → output frequency → output current → o1-01 selection.
Parameter o1-01 selects the content of the last monitor in this sequence.

No.

Name

Setting Range

Default

o1-01

Drive Mode Unit Monitor Selection

104 to 699

U1-04 (Control Mode) to

U6-99 (Option Monitors 20)

<1>

106 (U1-06)

<1> U2-oo and U3-oo parameters cannot be selected.

n

o1-02: User Monitor Selection after Power Up

Selects which monitor parameter is displayed upon power up by entering the 1- oo part of U1-oo. Certain monitors are

not available in some control modes.

No.

Name

Setting Range

Default

o1-02

User Monitor Selection after Power Up

1 to 5

1

Setting 1: Frequency Reference (U1-01)
Setting 2: Motor Direction
Setting 3: Output Frequency (U1-02)
Setting 4: Output Current (U1-03)
Setting 5: User Monitor

The monitor value selected by o1-01 will be displayed.

4.13 Advanced Drive Setup Adjustments

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual

185