Yaskawa AC Drive Z1000 User Manual

Page 191

Advertising
background image

Z1000

Software

Version

No.

(Addr.

Hex)

LCD Display

Name

Description

Values

PRG: 1012

and earlier

o4-17

(3100)

Set Time

0: Disabled

1: Enabled

Set/Reset Real Time

Clock

Sets the current date and time for the Real Time Clock.

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

PRG: 1013

and later

o4-17

(3100)

Set Time

0: — —

1: Set

2: Reset

Set/Reset Real Time

Clock

Sets the current date and time for the Real Time Clock.

0: — — No Setting

1: Real Time Clock Set

2: Real Time Clock Reset

Default: 0

Range: 0 to 2

Setting 0: — —

No Setting

Setting 1: Set

The HOA keypad shows the Clock Adjustment display. In Clock Adjustment Mode the user can adjust the Real Time Clock.

Setting 2: Reset

The Real-Time Clock data is cleared. A TIM fault will occur until o4-17 is set to 1 to set the Real Time Clock.

n

T1-01: Auto-Tuning Mode Selection

Sets the type of Auto-Tuning to be used.

Refer to Auto-Tuning for Induction Motors on page 142

for details on the different

types of Auto-Tuning.

No.

Name

Setting Range

Default

T1-01

Auto-Tuning Mode Selection

2, 3 (V/f)

2 (V/f)

Setting 2: Stationary Auto-Tuning for Line-to-Line Resistance
Setting 3: Rotational Auto-Tuning for V/f Control Energy Saving

n

T1-02: Motor Rated Power

Sets the motor rated power according to the motor nameplate value.

Note:

Use the following formula to convert HP to kW: kW = HP x 0.746.

No.

Name

Setting Range

Default

T1-02

Motor Rated Power

0.00 to 650.00 kW

Determined by o2-04

n

T1-03: Motor Rated Voltage

Sets the motor rated voltage according to the motor nameplate value. Enter the voltage base speed when the motor operates

above base speed. Enter the voltage needed to operate the motor under no-load conditions at rated speed to T1-03.

No.

Name

Setting Range

Default

T1-03

Motor Rated Voltage

0.0 to 255.0 V

<1>

200.0 V

<1>

<1> Values shown are specific to 200 V class drives. Double value for 400 V class drives.

n

T1-04: Motor Rated Current

Sets the motor rated current according to the motor nameplate value. Enter the current at the motor base speed.

No.

Name

Setting Range

Default

T1-04

Motor Rated Current

10.0 to 300.0% of drive rated

current

Determined by

o2-04

n

T1-05: Motor Base Frequency

Sets the motor rated frequency according to the motor nameplate value. If a motor with an extended speed range is used or

the motor is used in the field weakening area, enter the maximum frequency to E1-04 after Auto-Tuning is complete.

No.

Name

Setting Range

Default

T1-05

Motor Base Frequency

0.0 to 240.0 Hz

60.0 Hz

n

T1-06: Number of Motor Poles

Sets the number of motor poles according to the motor nameplate value.

4.13 Advanced Drive Setup Adjustments

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual

191

4

Start-Up Programming & Operation