Figure 3.46 – Yaskawa AC Drive Z1000 User Manual

Page 98

Advertising
background image

A

B

A – Cable tie hole

B – Cable hook

Figure 3.45 Control Terminal Wiring (2A0143 to 2A0396 and 4A0156 to 4A0590)

When setting the frequency by analog reference from an external potentiometer, use shielded twisted-pair wires (preparing

wire ends as shown in

Figure 3.46

) and connect the shield to the ground terminal of the drive.

A

E

B

C

D

A – Drive side
B – Connect shield to ground terminal

of drive.

C – Insulation

D – Control device side
E – Shield sheath (insulate with tape)
F – Shield

Figure 3.46 Preparing the Ends of Shielded Cables

NOTICE: The analog signal wiring between the drive and the operator station or peripheral equipment should not exceed 50 meters when

using an analog signal from a remote source to supply the frequency reference. Failure to comply could result in poor system performance.

3.9 Control Circuit Wiring

98

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual