0: Disabled
1: Square Root

n

b5-29: PI Square Root Gain

A multiplier applied to the square root of the feedback. If the PI Function is regulating the flow of a closed loop system by

using a pressure feedback, it may be convenient to view the square root of the PI output using monitor U1-37.

No.

Parameter Name

Setting Range

Default

b5-29

PI Square Root Gain

0.00 to 2.00

0.00

n

b5-30: PI Feedback Offset

Sets PI feedback Offset as a percentage of maximum frequency.

No.

Parameter Name

Setting Range

Default

b5-30

PI Feedback Offset

0.00 to 100.00%

0.00%

n

b5-34: PI Output Lower Limit

Sets the minimum possible PI controller output as a percentage of the maximum output frequency (E1-04). The lower limit is

disabled when set to 0.00%

No.

Name

Setting Range

Default

b5-34

PI Output Lower Limit

-100.0 to 100.0%

0.0%

n

b5-35: PI Input Limit

Sets the maximum allowed PI input as a percentage of the maximum output frequency (E1-04). Parameter b5-35 acts as a

bipolar limit.

No.

Name

Setting Range

Default

b5-35

PI Input Limit

0 to 1000.0%

1000.0%

n

b5-36: PI Feedback High Detection Level

Sets the feedback level used for PI feedback high detection. The PI feedback must exceed this level for longer than the time

set to b5-37 before feedback loss is detected.

No.

Name

Setting Range

Default

b5-36

PI Feedback High Detection Level

0 to 100%

100%

n

b5-37: PI Feedback High Detection Time

Sets the time that the PI feedback must exceed the value set to b5-36 before feedback loss is detected.

No.

Name

Setting Range

Default

b5-37

PI Feedback High Detection Time

0.0 to 25.5 s

1.0 s

n

b5-38, b5-39: PI Setpoint User Display, PI Setpoint Display Digits

When parameter b5-20 is set to 3, parameters b5-38 and b5-39 set a user-defined display for the PI setpoint (b5-19) and PI

feedback monitors (U5-01, U5-04).
Parameter b5-38 determines the display value when the maximum frequency is output and parameter b5-39 determines the

number of digits. The setting value is equal to the number of decimal places.

No.

Name

Setting Range

Default

b5-38

PI Setpoint User Display

1 to 60000

Determined by

b5-20

b5-39

PI Setpoint Display Digits

0 to 3

Determined by

b5-20

n

b5-40: Frequency Reference Monitor Content During PI

Sets the content of the frequency reference monitor display (U1-01) when PI control is active.

4.13 Advanced Drive Setup Adjustments